ENVIRONMENTAL
Operating Temperature
Range -40°F to +140°F
Operating Humidity 0-95% non-condensing
The control is mounted in an indoor/outdoor NEMA 3R
enclosure to resist moisture, dirt, insects, salt and other
corrosive elements. The enclosure can be panel mounted.
PHYSICAL
EC365/DST Series
Case
NEMA 3R Non-metallic enclosure with lockable hasp.
Weight Approximately 2 lbs.
Dimensions:
Width 6-1.2”
Height 9”
Depth 3-7/8”
EC365HPDST Hand Held Programmer
Weight Approximately 16 oz.
Dimensions:
Width 4”
Height 5”
Depth 2”
HOW
TO SPECIFY
Installer shall
furnish and install Paragon SunTracker™ II 365-Day
Electronic Lighting Controller with (SPST, DPST) contacts.
Contacts to be rated at (30 amperes resistive per pole up to
120 Vac or 40 amperes resistive per pole up to 277 Vac).
Control shall provide 7 days of power outage carry-over
without a battery. The one-channel control shall have
24-hour programming capability and Astro Dial feature to
provide automatic tracking of sunrise and sunset times in
order to automatically turn lights ON at dusk and OFF at
dawn. Control shall provide one additional ON and OFF event
as well as selectable daylight savings time adjustment and
automatic leap year correction. Control shall have
Skip-A-Day, offset to sunrise and/or sunset and manual
override. Control shall have adjustable latitude from 10°
to 70° northern or southern hemisphere. Control shall have
NEMA 3R non-metallic enclosure, with provision for
preventing unauthorized access. The control shall be
programmed via a hand held programmer.
|
ELECTRICAL
SPECIFICATIONS
| Model
No. |
Contact
Configuration |
Input
Voltage |
|
| EC365/DST1/120V |
SPST |
120
Vac
|
| EC365/DST2/120V |
DPST |
120
Vac
|
| EC365/DST2/277V |
DPST |
277
Vac
|
| EC365/HPST |
N/A |
9V Battery
operated |
Power Outage
Carry-over The program and time of day are maintained during
a power outage for a minimum of 7 days. A built in capacitor
eliminates the inconvenience of battery replacement.
Frequency 60
Hz
Power Consumption 4VA Max.
UL Listed, CSA Certified, and complies with FCC rules.
Output Switch
Rating
EC365/DST1
30 amp resistive or inductive at 120 Vac 6 amp Ballast
EC365/DST2/(120 & 277V)
40 amp resistive or inductive at 120-277 Vac 20 amp
ballast at 120-277 Vac Isolated contacts (switching contacts
separate from timer power supply)
|